Cancel

Siderise BH Brick Slip Horizontal Open State Cavity Barrier

Positively retained mechanical fix open state cavity barrier for restricting vertical fire spread whilst aiding ventilation and drainage in brick slip cladding systems. 

Balancing ventilation and drainage with fire compartmentation 

Siderise BH Brick Slip Horizontal Open State Cavity Barrier comprises a stone wool lamella core with vertically oriented fibres and an intumescent strip on its leading edge encapsulated within a colour coded polymer film. 

 
In normal service conditions, it allows ventilation and drainage of the cavity by leaving a gap behind the outer brick slip skin but closes the cavity in the event of fire to provide fire separation. The intumescent layer activates at around 130°C and starts to exfoliate until it fully closes the gap to form an effective fire seal within 5 minutes. 

Secure retention

Full-penetration mechanical fix brackets with bent tails for positively retaining the barrier help prevent it from shifting forward and ‘slipping’ off, thus reducing the moisture build-up risk associated with obstructing ventilation and drainage flow in the cavity, and also reducing any additional fire risk that can result from the formation of unprotected gaps between the substrate and barrier 

Compliant retention

The fixing method used to tightly secure the barrier to the internal structure enables them to remain firmly in place during the building’s lifetime, thus satisfying the mechanical retention requirements set out in the statutory guidance for fire safety in England, Wales, Scotland and Northern Ireland, as well as the advisory guidance published by CWCT 

60-year design life

BH Brick Slip Horizontal Open State Cavity Barrier has undergone EOTA TR 024 ‘Type X’ accelerated age testing to the harshest category, which replicates exposure to rain, UV, high temperatures, and frost and thaw cycles, to confirm long-term durability and suitability for buildings with a design life of 60 years or less 

Responsibly sourced

Manufactured in accordance with the framework standard for the responsible sourcing of construction products, BES 6001, to certification level ‘Good’, supporting the qualification for credits in sustainable building programmes such as BREEAM, LEED and DGNB 

Up to 2 hours fire resistance

Comprehensively tested to ASFP TGD19 ‘Fire Resistance Test of Open State Cavity Barriers’, it offers a range of insulation and integrity performance options to suit different project requirements. It has also undergone project-specific testing to confirm compatibility with various brick slip manufacturer systems. 

Third-party certified fire performance

Its fire resistance performance is IFC certified (IFCC 2144), and its reaction to fire performance to BS EN 13501-1: 2018 is Intertek US and UK certified 

Application

Tested within ventilated brick-slip cladding systems the Siderise Brick Slip Cavity Barriers comprise of the BH Brick Slip Horizontal Open State Cavity Barriers and the Siderise BV Brick Slip Closed State Vertical Cavity Barriers. Their combined use ensures that the brick slip system will drain moisture within the façade construction whilst maintaining airflow in normal service.

Siderise BH Brick Slip Horizontal Open State Cavity Barriers incorporate a continuous high-performance reactive intumescent strip which is bonded to the leading edge. In the event of fire, the intumescent rapidly expands and fully seals the purposely designed ventilation gap, between the barrier and the rear of the cladding, formed at the time of installation.

BH Brick Slip Horizontal Open State Cavity Barriers are compliant with current market requirements and has been tested to ASFP Guidance: ’Open State’ Cavity Barriers used in External Envelope or Fabric of Buildings, utilising principles of EN 1363-1, referred to as ASFP Technical Guidance Document –TGD 19 (EN 1364-6).

Intersections between the BH Brick Slip Horizontal Open State Cavity Barrier and BV Brick Slip Closed State Vertical Cavity Barriers are simply abutted, with RFT 120/45 foil tape applied as detailed in installation instructions provided separately.

Product Description

Siderise BH Brick Slip Horizontal Open State Cavity Barriers consist of a non-combustible stone wool lamella core, with reinforced aluminium foil faces.

The primary seal has a reaction to fire classification of Class A1 to BS EN 13501-1:2018, while the continuous intumescent strip on the exposed edge has a reaction to fire classification of Class E to EN 13501-1 and is designed to rapidly close the purposely designed ventilation gap in the event of fire. This is permitted by Regulation 7(3)(f) of Approved Document B.

The exposed leading edge is sealed with aluminium foil and additionally encapsulated in a polymer film, providing additional protection and a durable finish to the exposed edge.

Whilst the base material is water-repellent and non-hygroscopic, this predominantly enclosed arrangement provides additional weather protection to the core material. The product is designed to maintain an air gap for ventilation and moisture drainage within the brick slip cladding system under normal service conditions, whilst the intumescent material expands in the event of a fire to close the cavity.

The standard product length for both horizontal and vertical cavity barriers is 1200mm. BH horizontal cavity barriers are supplied as pre-cut strips.

For product identification purposes, the top edge of the film applied to BH cavity barriers is colour-coded and labelled to indicate the applicable fire performance classification. Refer to Table 1.

Fire Performance

Brick Slip Systems / Project Level Testing

Brick slip façade systems typically incorporate support rails behind the outer brick slips. In addition, the brick slips themselves may contain recesses or "frogs". Together, these features can create concealed voids within the façade build-up. These concealed voids should be considered as part of the fire performance assessment of the façade system, including where the façade is being assessed under the linear route provisions of Approved Document B.

Where project-specific arrangements fall outside the scope of available evidence, additional assessment and/or testing may be required. Siderise can provide project-specific testing and technical support where appropriate.

Relevant evidence may already be available through existing test reports, assessments and standard details. Please consult our Technical Services team for guidance on the applicability of available evidence to a specific project configuration.

Reaction to fire

This is the response of a material in contributing by its own decomposition to a fire to which it is exposed under specified conditions. Results are classified to BS EN 13501-1:2018 “Fire classification of construction products and building elements”.

The primary component of the Siderise BH Brick Slip Horizontal Open State Cavity Barrier comprises stone wool with aluminium foil facings. This component has third-party certified reaction to fire performance and is classified as A1 in accordance with EN 13501-1.

The intumescent component is classified as Class E in accordance with EN 13501-1. When exposed to fire, the intumescent material expands to close the designed ventilation gap within the cavity. The use of intumescent materials within cavity barriers is permitted by Regulation 7(3)(f) of Approved Document B (England and Wales).

Resistance to Fire

This is the ability of an element of structure or product to maintain its stability for a specific time period as determined by ‘integrity’ (E) and ‘insulation’ (I) as specified in the fire resistance test. Where appropriate results can then be classified in accordance with EN 13501-2.

Siderise has tested BH Brick Slip Horizontal Open State Cavity Barriers with a 25mm air gap to the ASFP TGD19 method. During the fire tests, the seals achieved full effective closure in under 5 minutes. Seal temperatures remained below a 180°C rise during this activation period and the assembly maintained a fire resistance performance of up to E 120 and I 120. Refer to Table 1 for details.

Please note: the fire resistance performance for BH Brick Slip Horizontal Open State Cavity Barriers, given in Table 1, relate to the performance of barrier in isolation, the overall performance of the system should be reviewed by Technical Services, with additional project level test evidence provided via the Siderise Innovation Centre if necessary.

Please see below tables for product fire performance ratings and applicable void sizes:

Table 1 : BH Fire Resistance to General Principles of ASFP - TGD 19 (EN 1364-6)

Product Ref Colour Max Air Gap (mm) Integrity (mins) Insulation (mins) Barrier Thickness (mm) Max Void (mm) Third-party Certification
BH25-120/90
Grey
25
120
90
Intumescent strip (1.5)
25
IFCC 2144
BH25-90/30
Green
25
90
30
75
425
IFCC 2144
BH25-60/60
Orange
25
60
60
90
425
IFCC 2144
BH25-120/120*
White
25
120
120
120
425
IFCC 2144
BH50-60/60
Blue
50
60
60
Intumescent strip (3.0)
50
IFCC 2144
BH50-30/30
Red
50
30
30
75
300
IFCC 2144
BH50-60/60
Blue
50
60
60
90
300
IFCC 2144

* Tested with min. 50mm thick stone wool thermal insulation (classified A1 to EN 13501-1) above and below the cavity barrier. See IFC Certification IFCC 2144 for further details.


Table 2: BH Fixing requirements and barrier dimensions

Product Range Void Range (mm) Air Gap (mm) Barrier Width (mm) Length (mm) Fixings
BH25
≤ 25
≤ 25
Intumescent strip (1.5)
1200
3no. Screws
26 - 40
≤ 25
15
1200
3no. Screws
41 - 45
≤ 25
20
1200
3no. Screws
46 - 75
≤ 25
Void - 25
1200
3no. Screws
76 - 250
≤ 25
Void - 25
1200
3no. RS 350 G/S
251 - 350
≤ 25
Void - 25
1200
3no. RS 450 G/S
351 - 400
≤ 25
Void - 25
1200
3no. RS 550 G/S
BH50
≤ 50
≤ 50
Intumescent strip (3.0)
1200
3no. Screws
51-65
≤ 50
15
1200
3no. Screws
66 - 70
≤ 50
20
1200
3no. Screws
71 - 100
≤ 50
Void - 50
1200
3no. Screws
101 - 250
≤ 50
Void - 50
1200
3no. RS 350 G/S
251 - 300
≤ 50
Void - 50
1200
3no. RS 450 G/S

The above fire performance relates to product only testing to TGD19, the overall void used within the system should be reviewed by Technical Services and supported by additional system specific project testing if necessary.

  • Brackets are available in two forms: (G) denotes galvanised steel brackets and (S) denotes stainless steel brackets.
  • Brackets must be installed at 400mm centres based on a 1200mm strip. For lengths ≤800mm 2no brackets must be used, with spacing reduced pro-rata. Lengths <100mm should be avoided by cutting down the adjacent barrier accordingly.
  • All brackets are to be suitably fixed to the substrate with non-combustible fasteners.
  • All brackets penetrate the product at mid-thickness. The protruding split ends should be counter-folded to retain the product, except for BH50-60/60 and BH25-120/120. For BH50-60/60, ensure the split end facing down overlaps with the intumescent face. For BH25-120/120, the bracket should overhang the barrier by 15mm then one of the split ends should be bent upwards and the other trimmed flush with the leading face of the barrier.
  • Please refer to separate BV-BH installation instructions.

Technical Specification

Table 3: BH Product Properties

Properties Value
Form Supplied 1200mm long. Supplied pre-cut in width to suit advised void size reduced by the ventilation gap required.
Product Finish Aluminium foil tape to top and bottom surfaces
Appearance Coloured tapes to indicate performance
Reaction to Fire The primary stone wool seal is Classified 'A1' to EN 13501-1
The reactive intumescent along the leading edge is Class 'E' to EN 13501-1. This is permitted by Regulation 7(3)(f) - Approved Document B for England & Wales.
Resistance to Fire For product fire performance see Table 1
Environmental
  • Stone wool core is recyclable.
Additional Information Available

The following information is available for download via the website:

  • Material Data Sheet
Technical Support

For technical advice, support, or to request a copy of a test or classification report - please contact: [email protected] 

For Installation Training or Site Inspections please contact: [email protected]

 

Context

The information in this datasheet is believed to be accurate at the date of publication. Siderise has a policy of continuous product improvement and reserves the right to alter or amend the specifications of products without prior notice. Siderise does not accept responsibility for the consequences of using the products described outside of the recommendations within this datasheet. Expert advice should be sought where there is any doubt about the correct specification or installation of Siderise products.

 
 

Products

Related products

Passive fire protection products designed to work holistically

Siderise BV Brick Slip Vertical Cavity Barrier
Ancillaries

Related ancillaries

Single source supply components for compatibility, performance and confidence

Siderise RS Series Fixing Bracket Pre-drilled
Siderise RFT Aluminium Foil Jointing Tape
Siderise FR-X Fire Rated Wet Zone Sealant
Contact us

We're here to help you

Talk to us

Call for our main switchboard

+44 (0) 1656 730 833

Ask technical

Email us for technical enquiries

[email protected]

Ask site services

Email us for site support

[email protected]

Complete a form

Complete the form for the right response

Contact us

Brick slip