Application
Siderise firestops for tops of walls provide a seal between the top of the compartment wall, partition, or fire-resistant suspended ceiling, and the structural soffit. The choice of material is determined by the performance requirement in terms of fire resistance (i.e. insulation and integrity) and size of the cavity.
Uses include:
Product Description
Siderise firestops for tops of walls comprise a single,
close dimensioned product with a unique pre-compressed
internal stonewool mineral fibre lamella core.
The materials are manufactured using a unique manufacturing process to provide a resilient compression which ensures a tight fit.
They are either supplied as pre-cut units to suit a quoted
cavity size or in sheet form for cutting on site.
The range of Siderise firestops for tops of walls
includes various types of products which are referenced
‘TW’ to designate the ‘Tops of Walls’ application.
The materials have been developed and tested at various
thicknesses to meet the fire and acoustic performance
requirements listed in Tables 1 and 3.
The design and manufacture of the range of Siderise firestops for tops of walls is based on proven fire performance to BS 476 : Part 20 :1987.
Please note that Siderise firestops for tops of walls can be supplied for higher fire ratings and for voids greater than 400mm, up to 1200mm.
The products have integral aluminium foil facings and are a functional smoke barrier.
In terms of ‘Reaction to Fire’, the products provide the following:
Table 1 - Fire performance and product sizes
Gap Height (mm) | Product Type | Seal Height x Thickness (mm) | Performance to BS 476: Part 20 | Cover Length (mm) |
---|
Integrity (mins) | Insulation (mins) |
---|
20 to 50 | TW-CB30 | Gap + 10 x 75 | 30 | 30 | 1200 |
| TW-FS60 | Gap + 10 x 90 | 60 | 60 | 1200 |
| TW-FS120 | Gap + 10 x 120 | 120 | 120 | 1200 |
51 to 100 | TW-CB30 | Gap + 5 x 75 | 30 | 30 | 1200 |
| TW-FS60 | Gap + 5 x 90 | 60 | 60 | 1200 |
| TW-FS120 | Gap + 5 x 120 | 120 | 120 | 1200 |
101 to 400 | TW-CB30 | Gap + 10 x 75 | 30 | 30 | 1200 |
| TW-FS60 | Gap + 10 x 90 | 60 | 60 | 1200 |
| TW-FS120 | Gap + 10 x 120 | 120 | 120 | 1200 |
NB: For bracket type and size please refer to Table 2
Table 2 - Fixing brackets
Bracket Ref. | Min Void Size (mm) | Max Void Size (mm) | No. of Brackets | Bracket Centres (mm) |
---|
B65/110 | 50 | 150 | 2 | 600 |
B195 | 151 | 240 | 2 | 600 |
B355 | 241 | 400 | 2 | 600 |
Siderise firestops for tops of walls provide excellent acoustic performance and can help to reduce room-to-room sound transmission. Their high performance is attributable to the mass of the mineral fibre core and the unique resilient lamella internal construction.
In accordance with BS EN ISO 140-3: 1995, BS 2750: Part 3: 1995 the Weighted Sound Reduction Index (Rw) values shown in Table 3 can be used.
These are based on laboratory tests for airborne sound transmission on a variety of lamella board constructions.
The installation of the products above a partition will significantly increase room-to-room attenuation. The precise value will depend upon the specifics of the ceiling construction. Advice is available on a project basis.
Table 3 - Acoustic performance
| Weighted Sound Reduction Index |
---|
Product Type | Thickness (mm) | Rw (dB) |
---|
TW-CB30 | 75 | 21 |
TW-FS60 * | 90 | 22 |
TW-FS120 | 120 | 25 |
* =Rw value interpolated from test results
Sound Research Laboratories Limited test report no. : C/99/SL/7743/I refers
Thermal conductivity : λ10 = 0.038 W/m.K (tested foil to foil)
Technical Specification
Siderise TW Firestops for Tops of Walls
Table 4: Product properties
Form supplied | Sheets 1200mm x 1200m x thickness |
| Cut strips 1200mm x cavity + compression x thickness |
| See Table 1 |
Colour | Silver, with coloured identification tape centrally located on product |
Finish | Aluminium foil |
Density | Nominal 75 kg/m3 |
Thermal conductivity | λ20= 0.038 W/m.K (tested foil to foil) |
Cavities | 20mm to 400mm |
Reaction to Fire | Class ‘A1’ to EN 13501-1 |
Resistance to Fire | 30 to 120 minutes (integrity/insulation) |
Environmental
Siderise Firestops for tops of walls are environmentally friendly.
- They contain no Volatile Organic Compounds (VOCs) and no very Volatile Organic Compounds (vVOCs).
- Zero Ozone Depleting Potential
- Zero Global Warming Potential
- Recyclable
The following information is available upon request or via download from the website:
- NBS Specification Clause
- Material Safety Data Sheet
- Cutting and Installation instructions
Technical Support
For technical advice or support please contact: technical.services@siderise.com
For Installation Training or Site Inspections please contact: site.services@siderise.com
Context
The information in this datasheet is believed to be accurate at the date of publication. Siderise has a policy of continuous product improvement and reserves the right to alter or amend the specifications of products without prior notice. Siderise does not accept responsibility for the consequences of using the products described outside of the recommendations within this datasheet. Expert advice should be sought where there is any doubt about the correct specification or installation of Siderise products.
Published Version: TW _v1_01_20211027_142